Scroll Top

Knowledge Base

no
Vent closed after filling and bleeding the system? – (fig. 1)
yes
  • Close vent and increase pressure (check filling level of overflow container)
yes
Solar liquid escaping from safety valve?
(recommended working pressure 3 bar)
no
  • Defective expansion vessel
  • MEV shut off?
    (Not permitted)
  • MEV too small?
    Recalculate, install additional unit if necessary
  • MEV admission pressure too high?
  • System filling pressure too high?
    Reduce as necessary
  • Incorrectly dimensioned safety valve?
    (Response pressure too low, eg. safety valve 3 bar, and is required by 6 or 8 bar?)
    Exchange if necessary
no
Solar circuit leakproof?
“Feel” every soldering point and screwed connection with the fingers
 
  • Empty system, rectify leak(s), fill and bleed system

  • The better the system is vented when filled the lower will be the number of faults caused by air in the system.
  • The system is vented by pumping the solar liquid through the system and through a tank filled with the same liquid until no more bubbles come out.
  • Pressure variations of 1–2 bar due to temperature variations during system operation are normal.
  • The system pressure should not decrease below the value of the static pressure + 0.5 bar, as otherwise a partial vacuum could be created in the upper area of the solar system and air may be drawn in.
Fig. 1
no
Is display on controller visible or does LED light up?
yes
  • Controller has no voltage supply. Check cable (power supply) and fuses
yes
Maximum store temperature reached?
no

Check maximum temperature.

Recommended:

  • Domestic water tank Tmax = 60°C (fig. 1)
  • Buffer storage tank Tmax = 90°C (fig. 2)

Change if necessary

yes
Does pump run after switching on manual switch?
no
  • Switch-on difference too high?
    Recomanded: (5–8 °C). Check!
  • Temperature sensor may be defective or not have a good contact
yes
Does controller switch pump?
no

Pump blocked!

  • Pump shaft seized up?
    Move shaft with screwdriver (with no voltage!)
  • Pump contaminated?
    Clean pump

If there is no effect, replace the pump

Controller defective. Send it to manufacturer.

Other reasons:

  • The store is hot, but below the maximum temperature. The sun’s radiation is not sufficient to reach the switch-on temperature difference. The behavior of the system in this case is satisfactory.
Fig. 1
Fig. 2
no
Is solar circuit pump running?
yes

Has tank reached its maximum temperature?

  • Domestic water tank Tmax = 60°C
  • Buffer storage tank Tmax = 90°C

If yes, behaviour is normal. Otherwise, check controller setting and correct if necessary

no
Does flowmeter show a flow?
yes
  • Air in system. Bleed it!
no

Is volumetric flow suitably high?
Recommanded flow for Euroterm ESK 2.5 SB collectors:

  • High flow system: Q = 40 l/h/m²
  • Low flow system: Q = 10 ÷ 15 l/h/m²
yes
  • Increase volumetric flow
yes
Return temperature almost the same as feed temperature?
no
  • Heat exchanger affected by limescale, blocked or too small?
    Descale, flush or recalculate/exchange heat Exchanger
  • Or are connections confused on solar circuit heat exchanger?
    Connect feed to top, return to bottom

Temperature difference:

  • High flow systems: Δt = 10 K
  • Low flow systems: Δt = 30 K
no
Are all shut-off elements open?
yes
  • Open fittings and secure against being closed unintentionally
yes
Is a flow displayed? ( fig. 1)
no
  • Check pressure, refill solar liquid if necessary until operating pressure achieved
  • Air probably in solar circuit. Bleed it (see below)
yes
Dirt trap blocked?
no
  • Clean dirt trap
yes
Return – flow preventer blocked?
(Recommended use of return-flow preventers with springs) fig. 2
 
  • Exchange return – flow preventer

The procedure for bleeding the solar circuit is as follows (because of the risk of vapour formation in times of high solar radiation this should be done if possible in the early morning or late afternoon):

  1. Open all vents.
  2. Increase system pressure with the help of a filling pump.
  3. Operate solar circuit pump with brief pulsating movements at maximum capacity.
  4. If necessary undo screw on recirculating pump, let air out and close again.
  5. Close all vents after successful bleeding.
Fig. 1
Fig. 2
yes
Solar circuit pump running at night?
no
  • Check controller function and sensors
yes
Collector temperature higher than outside temperature at night?
no
  • Check return-flow preventers in feed and return lines for proper function
yes
Thermal insulation of tank sufficient?
(Min. 100 mm flexible foam, 70 mm rigid foam)
no
  • Reinforce thermal insulation
no
Does thermal insulation fit closely to tank?
yes
  • Fit it correctly
no
Are all connections thermally insulated?
yes
  • Insulate connections
yes
Circulation pump running too long?
no
  • Change timer setting and supplement with Thermostat
yes
Switch off circulation pump and close shut-off valve for a night
no
  • Clean return-flow preventer, or exchange it.
    Are tank losses power?
  • Gravity circulation in circulation line is too strong. Install stronger return-flow preventer or electrical two-way valve after circulation pump.
  • Two-way valve open during pump operation, otherwise closed.
  • Connect pump and two-way valve in parallel electrically. Start circulation again.
no
Does solar circuit is well dimensioned? (table. 1)
yes
  • Check the solar circuit dimensions. Correct if is possible. If not replace it with correct pipe dimensiones
no
Are the pipes good and fully insulated?
yes
  • Insulate it completely
yes
Insulation exposed to external influences is damaged (it is recommended to be coated with aluminum sheet).
no
  • Check it. Use insulation with protective layer against UV rays and mechanical influences or already installed insulation coated with aluminum sheet
no
Are all connections thermally insulated?
 
  • Insulate connections
table 1

According to European standard EN 12976, solar thermal systems shall have been designed in such a way that prolonged high solar irradiation without heat consumption does not cause any situation in which special action by the user is required to bring the system back to normal operation.
The system can be protected against overheating in one of the following ways:

  1. The storage tank has reached the maximum temperature of 60оC, but still there is solar radiation. By stopping the collector pump and letting the collector fluid boil in the collector until it is dry and heats up to its stagnation temperature. The fluid is expanded into a suitable expansion vessel. Here it is important that evaporated solar medium cannot escape from an automatic air bleeder. A valve beneath the air bleeder can prevent this.

The picture shows the situation where fluid in conditions of stagnation would reach boiling point, which depends upon the pressure of the system.

The expansion vessel must be large enough to take the volume of liquid displaced from the collector due to evaporation, as otherwise the system would release the pressure via the safety valve and the system pressure would reduce too quickly after cooling. The response pressure of the safety valve should be 6 or 8 bar.

  • Calculation of the membrane (closed), expansion vessel:

First determine the volume of the system:

VA = VIT + VP + VK + VCM

VIT – exchanger
VP – circulating pump
VK – collectors
VCM  – solar circuit

Preset pressure of vessel (bar) is calculated by the following formula:

P0 =(hstat/10) + Pd

Pd – pressure of the glycol steam
hstat – static height of the collectors

The required nominal volume of the expansion tank is:

Vn,min =  (n × VA + VK + 0.1 × VCM) × (Pe +1)/ (Pe – P0)

Pe – final pressure in the expansion

Pe = 0,9 x Psv

Psv – pressure on which safety valve responds

The above operating condition means that the solar energy system is put under a certain stress. In other words, if the evaporated condition happens too frequently the heat transfer medium will age more rapidly.

In order to avoid this load, or to reduce it, the following measures can be used:

  1. In small and large systems, such as initial protection against stagnation we can use non isolated pot in which condenses steam formed in the initial phase of stagnation. The pot is placed on the expansion of the pipe under the automatic air valve on top of the collectors ( Fig. 1)
    Fig. 1
  2. By putting the collector at a steeper tilt angle, not only are the amount of excess heat and the stagnation times over the summer period reduced, but the yield in the winter is also increased.
  3. During holidays and annual vacations return-flow preventers are opened or pump run continuously day and night (regulated by means of digital differential automation). In this way the solar store can discharge via the collector at night- extra consumption of electricity.
  4. . In drainback systems, by stopping the circulation pump so that the collector is drained. The fluid is drained in additional drain back tank. (Fig. 2)
    Fig. 2
  5. If possible, the excess heat is used to heat the swimming pools, etc. If it is not possible, then excess heat is referred to heat exchanger (radiator, towel radiator, copper coil, fancoil etc.) that is located under roofing, in the basement or heat is referred to another medium, for further exploitation.
Privacy Preferences
When you visit our website, it may store information through your browser from specific services, usually in form of cookies. Here you can change your privacy preferences. Please note that blocking some types of cookies may impact your experience on our website and the services we offer.